1.15 Inverter POWERFUL Operation

Outline
In order to exploit the cooling and heating capacity to full extent, operate the air conditioner by
increasing the indoor fan rotating speed and the compressor frequency.
Detail
When [POWERFUL] button is pressed, the fan speed and target temperature are converted to
the following states for 20 minutes.
Operation mode
COOL
DRY
HEAT / RADIANT 1
FAN
AUTO
A
Ex: POWERFUL operation in cooling
Note:
For Floor Standing Type: FVXG Series
POWERFUL operation is only available in RADIANT 1 (RADIANT operation with heating), it is
not available in RADIANT 2 (RADIANT operation only).
Function and Control
Same as cooling / heating in
= 40 ~ 80 rpm (depending on the model)
Target temp.
18˚C
POWERFUL
ON
POWERFUL
OFF
Fan
A rpm
H tap
Set tap
Fan speed
H tap + A rpm
Dry rotating speed + A rpm
H tap + A rpm
H tap + A rpm
POWERFUL operation
It should be the lower limit of
cooling temperature.
20 minutes
Function of RA Indoor Unit
Target temperature
18°C
Lowered by 2 ~ 2.5°C
30 ~ 32°C
The target temperature is kept
unchanged.
It counts 20 minutes. also
in the remote controller.
Ending condition: "or" in 1 to 3
1. After the lapse of 20 minutes.
2. Operation OFF
3. POWERFUL operation is OFF.
(R13571)