Night Set Mode - Daikin 2MXS40H2V1B Service Manual

Inverter multi for 2 rooms h-series / g-series
Hide thumbs Also See for 2MXS40H2V1B:
Table of Contents

Advertisement

Function of RA Indoor Unit

1.10 NIGHT SET Mode

Outline
When the OFF timer is set, the NIGHT SET Mode is automatically activated. The NIGHT SET
Mode keeps the airflow rate setting.
Detail
The NIGHT SET Mode continues operation at the target temperature for the first one hour, then
automatically raises the target temperature slightly in the case of cooling, or lowers it slightly in
the case of heating. This prevents excessive cooling in summer and excessive heating in winter
to ensure comfortable sleeping conditions, and also conserves electricity.
<Cooling>
Target temperature
<Heating / Radiant>
65
30 minutes
+0.5˚C
TIMER operation
temperature shift
NIGHT SET Mode ON
Target temperature
TIMER operation
NIGHT SET Mode ON
0.5˚C
Operation stops
at the set hours
2˚C
1 hour later
SiBE121123_A
(R18034)
(R10871)