Toshiba MMU-AP0074YH-E Service Manual page 90

Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
controller
code
L10
L10
Target indoor
L17
L17
address
L18
L18
L20
L28
L28
SMMS (Series 1)
01: A3-IPDU1
error
02: A3-IPDU2
error
03: A3-IPDU1/A3-
IPDU2 error
04: Fan IPDU
error
05: A3-IPDU1 +
Fan IPDU error
06: A3-IPDU2 +
Fan IPDU error
07: All IPDU error
or Communication
error between
IPDU and I/F
circuit board or
Outdoor I/F circuit
board error
SMMS-i (Series 4)
L29
L29
Symbol O
signifies site of
IPDU error.
Location
AI-NET central
of
Description
control
detection
remote
controller
I/F
Outdoor
capacity not set
88
I/F
Outdoor unit
model mismatch
error
I/F
Cool / heat
switch unit error
AI-NET
Duplicated
Indoor
central control
98
unit
address
I/F
Too many
outdoor units
connected
46
I/F
Error in No. of
IPDUs
CF
Error detection
System status
condition(s)
All stop
Jumper wire provided on P.C.
board for servicing I/F P.C.
board has not been removed
as required for given model.
The outdoor unit model is
duplicate. The Cool/Heat
Flex series 1/2 are duplicate.
Only the target
The heating operation was
unit stopped
performed without the cool-
only setting configured in a
cool-only room where a cool/
heat switch unit is not
connected.
All stop
There is duplication in central
control address setting.
All stop
There are more than four
outdoor units.
All stop
Insufficient number of IPDUs
are detected when power is
turned on.
89
Check items (locations)
Check model setting of P.C.
board for servicing outdoor
I/F P.C. board.
• Check the outdoor unit
model.
• Check the remote controller
setting. (DN="0F")
• Check the cool / heat
switching unit.
Check the piping connection
of the switching unit.
(Miswiring of discharge gas /
suction gas)
Check the SVS / SVD valve
miswiring / misinstallation.
• Check central control
addresses.
• Check network adaptor
P.C. board (applicable to
AI-NET).
• Check No. of outdoor units
connected (Only up to 4
units per system allowed).
• Check communication
lines between outdoor
units.
• Check for defect in outdoor
P.C. board (I/F).
• Check model setting of
P.C. board for servicing
outdoor I/F P.C. board.
• Check connection of UART
communication connector.
• Check A3-IPDU, fan IPDU,
and I/F P.C. board for
defect.