No.
Component
10
Heat exchanger
1. Removing
PMV motor
2. Attaching
Procedure
1) Collect the refrigerant gas.
2) Remove the refrigerant pipe from the indoor unit.
3) Perform Step 1 of 1, Step 1 of 7, Step 1 of 8 and
Step 1 of 9.
Also remove the sensors.
4) Remove the screws fixing the pipe fixing to
remove it. (Ø4 X 8, 2)
5) When replacing the PMV motor, peel off the butyl
rubber put on the PMV itself until the PMV
appears, and loosen the nut fixing the PMV motor
with a double spanner to remove it.
6) Hold the heat exchanger and remove the screws
fixing the heat exchange separation board to
remove it.
(Ø4 X 8, 4)
7) Hold the heat exchanger and remove the screws
fixing the heat exchanger on the opposite side of
the heat exchange separation board to remove
the heat exchanger. (Ø4 X 8, 2)
1) Fix the components together with the sensors in
the following order: Heat exchanger ➝ Pipe fixing
➝ Drain pan ➝ Lower panel.
2) Reconnect the refrigerant pipe and purge air.
140
Remarks
Pipe fixing
PMV itself
PMV motor
PMV itself
Nut
Heat exchange separation board