Toshiba MMU-AP0074YH-E Service Manual page 59

Table of Contents

Advertisement

▼ To check all the indoor unit addresses using an arbitrary wired remote controller.
(When communication wirings of 2 or more refrigerant lines are interconnected for central control)
(Execute it while the units are stopped.)
You can check indoor unit addresses and positions of the indoor units in a single refrigerant line.
When an outdoor unit is selected, the indoor unit numbers of the refrigerant line of the selected unit are indicated
one after another and the fan and louvers of the indicated indoor units are activated.
1
Push and hold the TIME
At first, the line 1 and CODE No.
an outdoor unit.)
2
Push the
address.
3
Push the
button to confirm the system address selection.
• The address of an indoor unit connected to the selected refrigerant line is indicated on the LCD display and
its fan and louvers are activated.
4
Push the
button (left side of the button). Each time you push the button, the indoor unit
numbers of the selected refrigerant line are indicated one after another.
• Only the fan and louvers of the indicated indoor unit are activated.
◆ To select another system address
5
Push the
CL button to return to step
• After returning to step
6
Push the
button to finish the procedure.
and
buttons at the same time for more than 4 seconds.
(Address Change) are indicated on the LCD display. (Select
(left side of the button) and
2
, select another system address and check the indoor unit addresses of the line.
buttons repeatedly to select a system
2
.
58