Finishing

A. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear-
ances to combustibles as specifi ed. Framing or fi nishing
material closer than the minimums listed must be construct-
ed entirely of noncombustible materials (i.e., steel studs,
concrete board, etc).
Clearance to combustible material under the insert is 1/4
in. (6 mm). Clearance from top of fi replace opening for
combustibles extending 12 in. (305 mm) max. is 12 in.
(305 mm).
• Use leveling legs to raise insert minimum 1/4 in. (6 mm)
above combustible material or outer wrap of factory built
fi rebox.
Combustible facings must not extend behind the insert
surround. For non-combustible material specifi cations
refer to section 1.E.
46
Heat & Glo • Supreme-N-I30AU, Supreme-P-I30AU • 2222-900 Rev. X • 6/14
NON-COMBUSTIBLE FACING
Figure 11.1 Clearances to Mantels or other Combustibles
above Appliance
12 in.
(305 mm)
MAX.
MINIMUM CLEARANCE
TO COMBUSTIBLE
12 in.
MANTEL OR
(305 mm)
PROJECTION
MIN.