Installation sequence
Electrical connection
■ Route LV leads < 42 V and
cables > 42 V/230 V~/400 V~
separately.
■ Strip the insulation from the
cables as close to the terminals
as possible, and bundle tightly
to the corresponding terminals.
■ Secure cables with cable ties.
This ensures that, should there
be an error, for example when
detaching a wire, the wires can-
not drift into the adjacent voltage
area.
46
(cont.)
Note
If two components are connected to the
same terminal, both cores must be
pressed together into a single wire fer-
rule.
!
Please note
In terms of safety, the BUS cable
for the internal/external unit
(12 V or 43 V) does not count as
a LV lead.
The BUS cable must be routed
together with the 230 V cables.