Specification
(cont.)
Type AWT-AC
Cooling performance data
At 100 % according to
EN 14511
(A35/W18 °C, spread 5 K)
Rated cooling capacity
Compressor frequency
Fan speed
Power consumption
Energy efficiency ratio
EER
Air inlet temperature
Cooling mode
■ Min.
■ Max.
Heating mode
■ Min.
■ Max.
Heating water
at 10 K spread
Capacity
Minimum flow rate (al-
ways maintain)
Max. external pressure
drop (RFH) at min. flow
rate
Max. flow temperature
Electrical values
External unit
■ Rated voltage, com-
pressor
■ Max. rated current,
compressor
■ Starting current,
compressor
■ Starting current,
compressor with stal-
led armature
■ Starting current
(charging DC capaci-
tors)
■ Fuse protection
■ IP rating
241.A04
kW
4.2
Hz
60
rpm
870
kW
1.13
3.72
°C
15
°C
45
°C
–15
°C
35
l
2.8
l/h
600
mbar
590
°C
55
A
13.5
A
10.5
A
20
A
45
A
20
IP
24
241.A07
241.A10
8.8
10.0
65
55
650
650
2.63
2.80
3.35
3.57
15
15
45
45
–15
–15
35
35
2.8
3.8
820
1200
540
440
55
55
1/N/PE 230 V/50 Hz
15.7
19.6
15
10
25
25
< 35
30
20
20
24
24
Specification
241.A13
12.6
70
650
4.20
3.00
15
45
–15
35
3.8
1380
380
55
26.5
10
32
30
32
24
137