Viessmann Vitocal 242-S Installation And Service Instructions Manual page 40

Compact heat pumps, split version for heating and cooling operation
Hide thumbs Also See for Vitocal 242-S:
Table of Contents

Advertisement

Installation sequence
Connecting refrigerant lines
2x
6.
Tighten nuts with the following torques:
Type AWT-AC
Line
241.A04
Liquid line 7 6 mm
Hot gas line 7 12 mm
241.A07
Liquid line 7 10 mm
Hot gas line 7 16 mm
241.A10
Liquid line 7 10 mm
Hot gas line 7 16 mm
40
(cont.)
6. Type AWT-AC 241.A04:
■ Slide the supplied union nuts
(⁷⁄₁₆ UNF for liquid line, ¾ UNF for
hot gas line) over the refrigerant
lines from the external unit.
■ Flare the refrigerant lines from the
external unit.
■ Connect the supplied reducers
with copper sealing ring to the
connection pieces (twin nipple).
■ Secure the refrigerant lines from
the external unit onto the reducers,
using the union nuts.
Type AWT-AC 241.A07, A10 and
A13:
■ Slide the supplied union nuts
(⅝ UNF for liquid line, ⅞ UNF for
hot gas line) over the open end of
the refrigerant lines from the exter-
nal unit.
■ Flare the refrigerant lines from the
external unit.
■ Secure the refrigerant lines from
the external unit onto the connec-
tion pieces, using the union nuts.
Connection
to internal
unit
⅝ UNF
with reducer
⅝ x ⁷⁄₁₆
⅞ UNF
with reducer
⅞ x ¾
⅝ UNF
⅞ UNF
⅝ UNF
⅞ UNF
Torque in Nm
14–18
50–62
33–42
63–77
33–42
63–77