Installation sequence
Connecting refrigerant lines
!
2.
Please note
Contamination (e.g. metal
swarf) or moisture must not
enter the copper pipes.
Therefore, hold the pipe open-
ings downwards or tempora-
rily plug them.
Undo the nuts from connections C
and D on the refrigerant lines (liquid
line and hot gas line).
Type AWT-AC 241.A04:
Slide the nuts onto the refrigerant
lines prepared on site.
Type AWT-AC 241.A07, A10 and
A13:
Replace nuts with the supplied union
nuts (internal unit) (⅝ UNF for liquid
line, ⅞ UNF for hot gas line).
Tighten nuts with the following torques:
Type AWT-AC
Line
241.A04
Liquid line 7 6 mm
Hot gas line 7 12 mm
241.A07
Liquid line 7 10 mm
Hot gas line 7 16 mm
241.A10
Liquid line 7 10 mm
Hot gas line 7 16 mm
241.A13
Liquid line 7 10 mm
Hot gas line 7 16 mm
Connection to the internal unit
Note
We recommend using the pipe bends
supplied for connecting the refrigerant
lines. Depending on the installation con-
ditions, it may also be possible to con-
nect the refrigerant lines directly without
bends.
36
(cont.)
3. Flare the pipe ends.
4. Secure the pipes.
Connection
to external
unit
Torque in Nm
⁷⁄₁₆ UNF
¾ UNF
⅝ UNF
⅞ UNF
⅝ UNF
⅞ UNF
⅝ UNF
⅞ UNF
14–18
50–62
33–42
63–77
33–42
63–77
33–42
63–77