Chapter 5
Voltage Configuration
Powerware
5115 Tower UPS (500–1400 VA) User's Guide
®
Additional UPS Features
This section describes:
Changing the voltage configuration
Using the USB or DB-9 communication port
The Network Transient Protector
The DIP switches on the rear panel of each unit (see Figure 12) are used
to configure the output voltage and input voltage range.
1.
The UPS must be completely shutdown.
To turn off the UPS, press and hold the
seconds and then unplug the UPS from the power outlet.
2.
Set the DIP switches according to the configurations in Table 1.
3.
Plug the UPS power cord into a power outlet.
4.
Press and hold the
(approximately two seconds) to turn the UPS on.
button until you hear the UPS beep
UPS Rear Panel
Figure 12. DIP Switches
05146640 Rev C www.powerware.com
S
button for two
2
1
OFF
ON
25