Automatic Address Setting - Panasonic S-200PE1E8 Technical Data & Service Manual

Dc inverter, r410a
Hide thumbs Also See for S-200PE1E8:
Table of Contents

Advertisement

2-21-3. Checking indoor unit addresses
Use the remote controller to check the addresses of the indoor
units. Press and hold the
seconds or longer (simple settings mode, "ALL" appears on the
remote controller). Then press the
indoor address.
(For the system addresses of the No. 1 outdoor unit, each time the
button is pressed, the address changes as follows: 1-1, 1-2, ...)
The indoor unit fan operates only at the selected indoor unit.
Confirm the indoor unit address. (For the system addresses of
the No. 2 outdoor unit, the displayed addresses are 2-1, 2-2, ...)
Press the
button again to return to the normal remote
controller mode.
2-21-4. Indicating (marking) the indoor and outdoor unit combination number
Indicate (mark) the number after automatic address setting is completed.
(1) So that the combination of each indoor unit can be easily checked when multiple units are installed, ensure
that the indoor and outdoor unit numbers correspond to the system address number on the outdoor unit
control PCB, and use a magic marker or similar means which cannot be easily removed to indicate the
numbers in an easily visible location on the indoor units (near the indoor unit nameplates).
Example : (Outdoor) 1 – (Indoor) 1
(2) These numbers will be needed for maintenance. Be sure to indicate them.

2-22. Automatic Address Setting

2-22-1. Basic wiring diagram
Link wiring
A terminal plug (black) is attached to each of the outdoor unit control PCBs.
NOTE
At only one outdoor unit, leave the terminal plug short-circuit socket on the "Yes" side.
At all the other outdoor units, change the socket (from "Yes" to "No").
A maximum of 8 indoor units can be connected to 1 remote controller for group control.
System address
rotary switch on the
outdoor unit PCB
Terminal plate 1, 2
Outdoor unit
Terminal plate 1, 2
Indoor unit
Remote controller
button and
button for 4
button and select the
(Outdoor) 2 – (Indoor) 1
Refrigerant system No. 1
(Change setting to "1")
N
o
1 .
Inter-unit control
wiring
1-1
Refrigerant system No. 2
(Change setting to "2")
Change the terminal
plug (black) short-
N
o
2 .
circuit socket
2-1
Remote controller
2-21
Fig. 2-18
Refrigerant system No. 3
(Change setting to "3")
Change the terminal
plug (black) short-
N
o
3 .
circuit socket
3-1
Remote controller
2