1-9. ELECTRICAL WIRING

General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following
the wiring diagram.
(2) Provide a power outlet to be used exclusively for each unit and a circuit breaker for overcurrent protection should be
provided in the exclusive line.
(3) To prevent possible hazards from insulation failure, the unit must be grounded.
(4) Each wiring connection must be done in accordance with the wiring system diagram. Wrong wiring may cause the
unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility
for any damage or misoperation that occurs as a result of such unauthorized changes.
(7) Regulations on wire diameters differ from locality to locality. For field wiring rules, please refer to your LOCAL ELECTRICAL
CODES before beginning.
You must ensure that installation complies with all relevant rules and regulations.
(8) To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows:
The remote control wiring and the inter-unit control wiring should be wired apart from the inter-unit power wiring.
Use shielded wires for inter-unit control wiring between units and ground the shield on both sides.
(9) If the power supply cord of this appliance is damaged, it must be replaced by a repair shop designated by the manufacturer,
because special-purpose tools are required.
Recommended Wire Length and Wire Diameter for Power Supply System
Outdoor unit (3-Phase)
Wire size
U-200PE1E8
14 mm
U-250PE1E8
14 mm
Indoor unit
S-200PE1E8
S-250PE1E8
Control wiring
(C) Inter-unit (between outdoor
and indoor units) control wiring
0.75 mm
2
(AWG #18)
Use shielded wiring*
Max. 1,000 m
NOTE
*1 With ring-type wire terminal.
*2 When the type "E1" is used with maximum length of 500 m for group control, and if the remote controller for the group control
is wireless, the maximum length will be 400 m.
Time delay
(A) Power supply
fuse or circuit
Max. length
capacity
2
116 m
2
96 m
(B) Power supply
Time delay fuse or
circuit capacity
2
2.5 mm
Max. 50/30 m
10/16 A
(D) Remote control wiring
2
0.75 mm
(AWG #18)
1
2
Max. 500 m*
15 A
20 A
1-18