9. HOW TO INSTALL THE INDOOR UNIT

High Static Pressure Ducted Type (E1 Type)
1. Required Minimum Space for Installation and Service (200, 250 Types)
The installation instructions that come with the indoor unit
describe how to use it in combination with the U-200PE1E8
and U-250PE1E8 outdoor units.
Please refer to the following when using it in combination
with the U-200PE1E8 and U-250PE1E8 outdoor units.
This air conditioner is usually installed above the ceiling so
that the indoor unit and ducts are not visible. Only the air
intake and air outlet ports are visible from below.
The minimum space for installation and service is shown in
Fig. 1-19.
It is recommended that space be provided (600 × 600 mm) for checking and servicing the electrical system.
Fig. 1-20 shows the detailed dimensions of the indoor unit.
479
300
41
100
100 50
23
178
2
100 100
60
320
43
1310
1070
10 100P=1000
106
28-ø3.5 (Holes all around)
44
26-ø3.5 (Holes all around)
9 100P=900
964
1200 (Suspension bolt pitch)
67
1310
42
364
(236)
364
1334
1428
Min. 600
(Space for
service)
Air suction
side
Min. 700
(Space for
Refrigerant
service)
Min. 610
Min. 130
Refrigerant tubing joint (liquid tube ø12.7 mm) (Flare nut)
1
Refrigerant tubing joint (gas tube ø25.4 mm) (Brazing)
2
Power supply outlet
3
Drain port (O.D. 32 mm)
4
Duct connection for suction
5
Duct connection for discharge
6
4 - 37 12
(Hole for suspension bolt)
67
1-39
Unit: mm
1170
(Suspension bolt pitch)
1100
Inspection
Electrical
access
component box
(600 600)
tubing
Drain pan
Ceiling face
Drain port
Fig. 1-19
Unit: mm
Fig. 1-20
1