1.1 Keybus Wiring

The 4-wire KEYBUS (red, black, yellow and green) is the communication connection between the control panel and all modules.
The 4 KEYBUS terminals of all modules must be connected to the 4 KEYBUS terminals of the main control panel.
The following rules must be followed when wiring the Keybus:
Minimum 22 AWG wire, maximum 18 AWG (2-wire twisted preferred
Do NOT use shielded wire
Modules can be home run, connected in series or can be T-tapped pro-
vided that the maximum wire distance from the control panel to any
module does not exceed 1,000 feet (305m)
No more than 3,000 feet (915m) of wire can be used in total

1.2 Zone Wiring

Zones can be wired for Normally Open, Normally Closed Contacts with
Single-end-of-line (SEOL) resistors or Double End-of-Line (DEOL) resis-
tors. Observe the following guidelines
For UL Listed Installations use SEOL or DEOL only.
Minimum 22 AWG wire, maximum 18 AWG
Do NOT use shielded wire
Wire run resistance shall not exceed 100Ω. Refer to the chart below
Burglary Zone Wiring Chart
Wire
Gauge
22
20
19
18
Figures are based on maximum wiring
Section [001]-[004] Selects Zone Definition
Section [013] Opt [1] Selects Normally Closed or EOL resistors
Section [013] Opt [2] Selects Single EOL or Double EOL resistors.
Section [101]-[108] Opt [14], [15], [16] Selects Normally Closed Single
EOL or Double EOL for on-board zones (PC1864, PC1832,Zone 1-8;
PC1616, Zone 1-6),
Zone Status - Loop Resistance/Loop Status
• Fault - 0Ω (shorted wire/loop)
• Secure - 5600Ω (contact closed)

1.3 Zone Expanders

Zone expanders add zones in groups
of eight to the Alarm system. Module
jumpers J1,J2,J3 are required to
assign zones to these modules.
Jumper settings for PC5108v2 are
shown here.
PC5108v1.0 supports first 32 zones only.
PC5700 enrolls as two modules
Do NOT use PC5108v1 &v2 on the same
panel.0

1.4 Bell Wiring

These terminals supply 700mA of current at 12VDC for commercial installations and 11.1-12.6 VDC for
residential installations (e.g.DSC SD-15 WULF). To comply with NFPA 72 Temporal Three Pattern
requirements: Program Section [013] Opt [8] ON.
NOTE: Steady, Pulsed alarms are also supported.
The Bell output is supervised and power limited by 2A PTC. If unused, connect a 1000Ω resistor across Bell+
and Bell- to prevent the panel from displaying a trouble. See [ ][2].
2
Maximum wire Length to
End-of-line Resistor
(feet/meters)
3000 / 914
4900 / 1493
6200 / 1889
7800 / 2377
resistance of 100Ω
Module
Jumpers
J1
J2
J3
ON
ON
ON
OFF ON
ON
ON
OFF ON
OFF OFF ON
ON
ON
OFF
OFF ON
OFF
ON
OFF OFF
OFF OFF OFF
WWW.DIYALARMFORUM.COM
CONTROL
Normally Closed Loops - Do NOT use for UL Installations
.
Single End-of-Line Resistor Wiring
Double End-of-Line Resistor Wiring
• Tamper - infinite (broken wire, open)
• Violated - 11,200Ω (contact open)
Zones
Assigned
Zones Disabled
Zones 09-16
Zones 17-24
Zones 25-32
Zones 33-40
Zones 41-48
Zones 49-56
Refer to to the associated installation sheet for Jumper locations for the
Zones 57-64
PC5108v1, or PC5700
150' (46m)
500' (152m)
150' (46m)
PANEL
500' (152m)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerseries pc1832Powerseries pc1864Pc1808

Table of Contents