Power Supply Waveforms Check; Inverter Units Refrigerant System Check - Daikin FLKS25BVMB Service Manual

Inverter pair floor / ceiling suspended dual type b-series
Hide thumbs Also See for FLKS25BVMB:
Table of Contents

Advertisement

SiBE05-311

5.1.7 Power Supply Waveforms Check

Check No.10
Measure the power supply waveform between pins 1 and 3 on the terminal board, and check
the waveform disturbance.
[Fig.1]

5.1.8 Inverter Units Refrigerant System Check

Check No.11
Service Diagnosis
Check to see if the power supply waveform is a sine wave (Fig.1).
Check to see if there is waveform disturbance near the zero cross (sections circled in Fig.2)
Refrigerant system check
Is
the discharge
thermister disconnected from
the holder?
NO
Is any moisture
found in sight glass.
NO
Check for gas leaks.
See the section on insufficient gas
detection.
YES
[Fig.2]
YES
YES
Conduct the check after operating the
equipment for a sufficient length of time.
Check
Correct the problem.
Conduct vacuum drying.
Replace the refrigerant.
(R1445)
109