D7412Gv2 Faceplate; Figure 37: D7412Gv2 Faceplate - Bosch D9412GV2 Operation And Installation Manual

Hide thumbs Also See for D9412GV2:
Table of Contents

Advertisement

D9412GV2/D7412GV2 | Operation and Installation Guide | 14.0 Faceplates
14.2

D7412GV2 Faceplate

Figure 37: D7412GV2 Faceplate

LEDs Off When Normal
YEL
Charging Status
1
Low Battery - 12.1 VDC
RED
2
10.2 VDC - Battery Load Shed
CLASS 2 TRANSFORMER
16.5 VAC 40 VA 60 Hz
Model D1640
Internally Fused - Do Not short
Requires Unswitched Outlet
Do Not Share With Other Equipment
BATTERY NEGATIVE ONLY
CAUTION:
Do not connect 24 V to terminals.
Maximum charging current 1.4 A
BATTERY POSITIVE ONLY
3
4
GROUND FAULT DETECT
5
PHONE LINE
SEIZED
6
1 - Charging status LED (yellow)
2 - Low battery LED (red)
3 - Color-coded battery leads
4 - Ground fault detect enable
5-
Phone LED (red)
6 - Tip
7
Telephone cord connector
68
F01U003799-01
Incorrect wiring will
damage this equipment.
Suitable for dry indoor
use only.
Devices powered by the
AUX power output must
be supervised.
Refer to D9412GV2/D7412GV2 Approved Applications Compliance Guide (P/N: F01U003639)
Refer to the D9412GV2/D7412GV2 Approved Applications Compliance Guide (P/N: F01U003639)
For System Wiring Diagram, Issue A and for Compatible Smoke Detectors
For System Wiring Diagram, Issue A and for Compatible Smoke Detectors
Minimum system requirements for Classification in accordance with ANSI/SIA CP-01-2000:
UL Listed and Classified control unit Model D9412GV2, D7412GV2, or D7212GV2;
UL Listed and Classified keypad Model D1256, D1257, D1260, D1255, D1255R, or D1255RW;
UL Listed Local Bell
The Power Supply provides a maximum of 1.4 Amps for the Control Panel and all
Accessory Devices. For System Loading, refer to D9412GV2/D7412GV2
Operation and Installation Guide (P/N: F01U003641).
All external connections except Terminal 5 (battery positive) are inherently power
limited. Requirements for battery standby time might reduce allowable output.
CAUTION:
See D9412GV2/D7412GV2 Operation and Installation Guide
+ AUX POWER
(P/N: F01U003641) for Power Requirements relating to Terminals 6 and 7 .
WARNING!
Multi-Battery installation requires
Avoid damage to Panel.
Model D122/D122L Dual Battery
Harness. Improper installation can
be a fire hazard.
This equipment should be installed in accordance with the NFPA 70 (National Electrical Code)
PROGRAMMABLE
RELAY A
and NFPA 72 (National Fire Alarm Code) for Local, Central Station, Proprietary and Household Fire
ALARM OUTPUTS
Warning Systems and under the limits of the Local Authority Having Jurisdiction (National Fire
Terminals
Protection Association, Battermarch Park, Quincy, MA 02269). Printed information describing
6
and
7
proper installation, operation, testing, maintenance, evacuation planning and repair service is to
RELAY B
be provided with this equipment.
SWITCHED AUX
D7412GV2 Control Panel is UL Listed for Central Station, Local, Auxiliary, Proprietary, and Household
Terminal
Fire Alarm, and Central Station, Local, Police Station Connect, Household Burglar Alarm and
RELAY C
8
Encrypted Line Security when communicating via a network.
System is intended to be checked by a Qualified Technician at least every 3 years.
The types of initiating circuits for which the control panel has been approved are A, M, W, SS.
COMMON
The types of signaling the control panel has been approved for are: DAC, OT, NC
EARTH GROUND
Point 1 Point 2
Enabled
Disabled
ON when
PHONE
communicating
RED
LED
OFF when idle
PHONE LINE SEIZED
11
12
13
TIP
RING
TELCO CORD
MODEL D161
TIP
RING
TELCO
8
7
D7412GV2
Commercial Protected-Premises Control Panel
POWER SUPPLY REQUIREMENTS
Battery: Replace every 3 to
5 years with one or two Model
D126 or D1218 12V Lead Acid
Batteries.
VOLTAGE RANGES
Open
3.7 - 5.0 VDC
Normal
2.0 - 3.0 VDC
Short
0.0 - 1.3 VDC
Point 3 Point 4
Point 5 Point 6
Point 7 Point 8
14
15
16
17
18
19
20
21
9
8-
Ring
9-
S3, Point 8 EOL selection
10- Operation monitor LED (green)
11- Accessory connector
12- Programming connector
13- Reset pin
14- SDI quick connector
Bosch Security Systems, Inc. | 7/09 | F01U003641-04
SDI Connector
Reset Pin
Disable All Except Battery
Charging And Programming
PERIPHERAL DEVICE CONNECTIONS
RED
POWER +
YELLOW
DATA BUS A
GREEN
DATA BUS B
BLACK
COMMON
N.F.P.A.
ZONEX OUT 1
Style 4.0
Signaling
Line
Circuits
ZONEX IN 1
26
NOT USED
25
NOT USED
24
ZONEX POWER +
23
ZONEX COMMON
Point 8
D5200/D5360
PROG CONN
S3 Option
Closed = 1KΩ EOL
Normal Operation
Open =AB-12 UL
Bell Box 220 KΩ
22
GRN
10
11
14
13
12