Heating High Pressure Control; Heating Overload Protective Control; Indoor Heat Exchanger Temperature - Mitsubishi Heavy Industries FDT Series Technical Manual
Notes (1) When the indoor heat exchanger temperature is in the range of B~C ºC, the speed is reduced by 4 rps at each 10seconds.
or higher continues for 1 minute, the compressor is stopped.
(3) When the indoor heat exchanger temperature is in the range of A~B ºC, if the compressor command speed is been maintained and the operation has contin-
ued for more than 10 seconds at the same speed, it returns to the normal heating operation.
(4) Indoor blower retains the fan tap when it enters in the high pressure control. Outdoor blower is operated in accordance with the speed.
Temperature list
RPSmin < 50
50 < = RPSmin < 115
115 < = RPSmin < 120
120 < = RPSmin
Note (1) RPSmin: The lower one between the outdoor speed and the compressor command speed