Installation Procedure - Mitsubishi Heavy Industries FDT Series Technical Manual

Hyper inverter packaged air-conditioners fdt, fdf, fdtc, fden, srk, fdc, fdum series
Hide thumbs Also See for FDT Series:
Table of Contents

Advertisement

Request
Be sure not to install R/C at a place where temperatures around the installation surface of R/C may differ largely from
actual room temperature.
Difference between detected temperature and actual room temperature could cause troubles.
The correction for detected temperature by the R/C cannot offset such temperature difference because it corrects the
detected temperatures itself.
Request
Do not install the R/C at a place where it is exposed to direct sunlight or where surrounding air temperature exceeds 40°C
or drops below 0°C.
It could cause discoloration, deformation, malfunction or breakdown.

Installation procedure

Dimensions (Viewed from front)
F i xing holes
3 7
To remove the upper case from the bottom cases of R/C
· Insert the tip of flat head screwdriver or the like in the
recess at the lower part of R/C and twist it lightly to
remove.
Take care to protect the removed upper case
from moisture or dust.
Connect wires from X and Y terminals of R/C to X and Y
terminals of indoor unit.
R/C wires (X, Y) have no polarity.
In case of embedding wiring
Embed the switch box and the R/C wires beforehand.
Seal the inlet hole for the R/C wiring with putty.
If dust or insect enters, it could cause electric shocks,
fire or breakdown.
2 3
2 3
1 2 0
(When the wiring is retrieved "Backward")
PCB side (Viewed from rear)
S e nsor
1 9
5 0
8
-
260
-
'12 • PAC-T-173
Terminal Block
U S B port
Conduit
Wall
L o cknut
Bushing
2 0 0
R/C cable
S w itch box
S e al with putty