Setting and actual values
Static pressure
Supply pressure (flow pres-
sure)
= for natural gas E
= for natural gas LL
= for LPG
Tick gas type
Carbon dioxide content
CO
2
for natural gas
■ At lower heating output
■ At upper heating output
For LPG
■ At lower heating output
■ At upper heating output
Oxygen content O
2
■ At lower heating output
■ At upper heating output
Carbon monoxide content
CO
■ At lower heating output
■ At upper heating output
Set value Commis-
Date
Signature
≤ 57.5
mbar
mbar
17.4-25
mbar
17.4-25
mbar
42.5-57.5
% by vol.
7.5-9.6
% by vol.
7.5-9.6
% by vol.
9.0-11.3
% by vol.
9.0-11.3
% by vol.
3.8-7.3
% by vol.
3.8-7.3
ppm
< 1000
ppm
< 1000
Commissioning/service reports
Mainte-
sioning
nance/
Service
173