Viessmann Vitodens 200-W Installation And Service Instructions Manual page 100

125 and 150 kw wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Code 2
Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
A5:5
With heating circuit pump
logic function (economy
mode): Heating circuit
pump "OFF" when the
outside temperature (AT)
is 1 K higher than the set
room temperature (RT
AT > RT
weather-compensated
control units)
Parameter address
A5:...
1
2
3
4
5
6
7
to
15
100
)
set
+ 1 K (only for
set
With heating circuit pump logic function: Heating cir-
cuit pump "OFF"
AT > RT
+ 5 K
set
AT > RT
+ 4 K
set
AT > RT
+ 3 K
set
AT > RT
+ 2 K
set
AT > RT
+ 1 K
set
AT > RT
set
AT > RT
- 1 K
set
AT > RT
- 9 K
set
Possible change
Note
"Important" observe for
code "A3".
A5:0
Without heating circuit
pump logic function
A5:1
With heating circuit pump
to
logic function: Heating cir-
A5:15
cuit pump "OFF"; see fol-
lowing table
(cont.)