Viessmann Vitodens 200-W Installation And Service Instructions Manual page 133

125 and 150 kw wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Fault codes
(cont.)
Dis-
Const.
played
fault
code
F3
X
F6
X
F8
X
F9
X
FA
X
FC
X
Weath.-
System char-
comp.
acteristics
X
Burner in a fault
state
X
Burner in a fault
state
X
Burner in a fault
state
X
Burner in a fault
state
X
Burner in a fault
state
X
Burner in a fault
state
Troubleshooting
Cause
Measures
Flame signal
Check ionisation
is already
electrode and con-
present at
necting cable.
burner start
Press reset button
R.
Boiler water
Replace boiler wa-
temperature
ter temperature
sensor tem-
sensors.
perature val-
ues vary too
widely from
one another
Fuel valve
Check gas train.
closes too
Check both control
late
paths.
Press reset button
R.
Fan speed
Check fan, fan con-
too low during
necting cables and
burner start
power supply;
check fan control.
Press reset button
R.
Fan not at
Check fan, fan con-
standstill
necting cables and
fan control.
Press reset button
R.
Gas train faul-
Check gas train.
ty, faulty mod-
Check flue sys-
ulation valve
tem.
control or flue
Press reset button
gas path
R.
blocked
133