Viessmann Vitodens 200-W Installation And Service Instructions Manual page 140

125 and 150 kw wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Troubleshooting
Repair
(cont.)
1. Check whether the flue gas temper-
ature sensor is correctly inserted.
See previous diagram.
2. If necessary, correct the position of
the flue gas temperature sensor or
replace faulty flue gas temperature
sensor.
Checking the fuse
A
1. Switch off the power.
2. Release the side closures and pivot
the control unit down.
140
3. Press reset button R and repeat com-
missioning.
The check is repeated until it is com-
pleted successfully.
F1
3. Remove cover A.
4. Check fuse F1 (see connection and
wiring diagram).