Boiler/group "2"
Coding in the delivered condition
08:...
Maximum burner heating
output in kW in the case
of a multi boiler system
0d:0
Do not adjust
0E:0
Do not adjust
13:1
Do not adjust
14:1
Do not adjust
15:1
Do not adjust
21:0
No service interval (hours
run) selected
23:0
No time interval for burn-
er service
24:0
No "Service" display
28:0
No burner interval igni-
tion
2E:0
Do not adjust
2F:0
Venting program/fill pro-
gram disabled
30:3
Boiler circuit pump speed
controlled via 0-10 V in-
terface (do not adjust)
38:0
Status burner control unit:
Operational (no fault)
(cont.)
Possible change
08:0
to
08:199
21:1
to
21:100
23:1
to
23:24
24:1
28:1
to
28:24
2F:1
2F:2
38:≠0
Code 2
Maximum burner heating
output adjustable from 0 to
199 kW (limited by boiler-
specific parameters) in
steps of 1 kW
Number of hours run be-
fore the burner should be
serviced is adjustable from
100 to 10,000 h
One adjusting step ≙
100 h
Interval adjustable from 1
to 24 months
"Service" display (the ad-
dress is automatically set
and must be manually re-
set after a service has been
carried out)
Interval adjustable from 1 h
to 24 h. The burner is force-
started once every 30 s
(only when operating with
LPG).
Venting program enabled
Fill program enabled
Status burner control unit:
Faults
91