Repair - Viessmann Vitodens 200-W Installation And Service Instructions Manual

125 and 150 kw wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Repair

Checking the outside temperature sensor (weather-compensa-
ted control unit)
X3
200
100
80
60
40
20
10
8
6
-20 -10
0
Temperature in °C
Sensor type: NTC 10 kΩ
1. Pull plug "X3" from the control unit.
10 20 30
2. Test the resistance of the outside
temperature sensor across terminals
"X3.1" and "X3.2" on the disconnec-
ted plug and compare it with the
curve.
3. Where actual values deviate severely
from the curve values, disconnect the
wires at the sensor and repeat test on
the sensor itself.
4. Depending on the result, replace the
lead or the outside temperature sen-
sor.
Troubleshooting
135