Cj1W-Int01 Interrupt Input Unit (16 Points) - Omron NJ501-1 Series User Manual

Machine automation controller nj-series cpu unit hardware
Table of Contents

Advertisement

Appendices
 CJ1W-INT01 Interrupt Input Unit (16 Points)
Name
Model
Rated Input Voltage
Allowable Input Voltage Range
Input Impedance
Input Current
ON Voltage/ON Current
OFF Voltage/OFF Current
ON Response Time
OFF Response Time
Number of Circuits
Number of Simultaneously ON Points 100% (16 points/common) simultaneously ON (24 VDC)
Insulation Resistance
Dielectric Strength
Internal Current Consumption
Weight
Accessories
Circuit Configuration
External connection and terminal-
device variable diagram
* Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed
on the Units.
Note Interrupt Input Units can be used as normal Basic I/O Units. They cannot be used to start I/O interrupt tasks.
A-18
16-point Interrupt Input Unit with Terminal Block
CJ1W-INT01
24 VDC
20.4 to 26.4 VDC
3.3 k
7 mA typical (at 24 VDC)
14.4 VDC min./3 mA min.
5 VDC max./1 mA max.
0.05 ms max.
0.5 ms max.
16 (16 points/common, 1 circuit)
20 M between external terminals and GR terminal (at 100 VDC)
1,000 VAC between external terminals and GR terminal for 1 minute at a leakage current of 10 mA
max.
80 mA max.
110 g max.
None
Signal
name
3.3 kΩ
Jxx_Ch1_In00
to
Jxx_Ch1_In15
COM
Input indicator
COM
Temperature characteristics for
simultaneously ON points
18
16
14
Input voltage: 26.4 VDC
12
10
8
6
4
2
0
0
10
20
30
40
50
Ambient Temperature
Signal
Connec-
name
tor pin
Jxx_Ch1_In00
A0
B0
Jxx_Ch1_In02
A1
B1
Jxx_Ch1_In04
A2
B2
Jxx_Ch1_In06
A3
B3
Jxx_Ch1_In08
A4
B4
Jxx_Ch1_In10
A5
B5
Jxx_Ch1_In12
A6
B6
Jxx_Ch1_In14
A7
B7
COM
A8
B8
• Up to two Interrupt Input Units can be
mounted to the CPU Rack. They must
be connected as one of the five Units
immediately next to the CPU Unit. If an
Interrupt Input Unit is connected in any
other position, an Incorrect Unit/Expan-
sion Rack Connection error will occur.
• Set the pulse width of signals input to
the Interrupt Input Unit so they satisfy
the following conditions.
16 points at 45°C
12 points at 55°C
(°C)
60
Signal
name
*
Jxx_Ch1_In01
Jxx_Ch1_In03
Jxx_Ch1_In05
Jxx_Ch1_In07
Jxx_Ch1_In09
Jxx_Ch1_In11
Jxx_Ch1_In13
Jxx_Ch1_In15
COM
• The polarity can be connected in either direction.
NJ-series CPU Unit Hardware User's Manual (W500)
OFF
0.5 ms min.
ON
0.05 ms min.
24 VDC

Advertisement