3-5-4

B7A Communications Specifications

Item
Transmission
One-way time-sharing multiplex transmissions
method
Transmission delay
High-speed
(communications
Standard
delay on
transmission path)
CJ1W-B7A14
Transmission points
CJ1W-B7A04
CJ1W-B7A22
External power
12 to 24 V DC (allowable voltage range: 10.8 to 26.4 V)
*1
supply voltage
CJ1W-B7A14
External supply
CJ1W-B7A04
*2
current
CJ1W-B7A22
High-speed
Minimum input
*3
time
Standard
High-speed
Transmission
distance
Standard
VCTF, 0.75 mm
VCTF, 0.75 mm
Cables
Shielded cable, 0.75 mm
Shielded cable, 0.75 mm
*1 We recommend OMRON S8-series Power Supply Units for the external power supplies.
*2 The capacity of the external supply current does not include the capacity required by the B7A Link Terminal.
*3 The minimum input time is the minimum time required by the B7A Interface Unit to read the input signals from the CPU
Unit.
*4 When a common power supply is used, the B7A Interface Unit and B7A Link Terminal are supplied by the same external
power supply.
*5 When separate power supplies are used, the B7A Interface Unit and B7A Link Terminal are supplied by separate external
power supplies.
NJ-series CPU Unit Hardware User's Manual (W500)
Specifications
3 ms typical, 5 ms max.
19.2 ms typical, 31 ms max.
64 inputs (4 ports)
64 outputs (4 ports)
32 inputs (2 ports), 32 outputs (2 ports)
40 mA min.
150 mA min.
80 mA min.
16 ms
2.4 ms
Power supply on one side
*4
(common power supply)
Power supply on both sides
*5
(separate power supplies)
Power supply on one side
*4
(common power supply)
Power supply on both sides
*5
(separate power supplies)
2
, 3 conductors (power supply on one side (common power supply))
2
, 2 conductors (power supply on both sides (separate power supplies))
2
, 3 conductors (power supply on one side (common power supply))
2
, 2 conductors (power supply on both sides (separate power supplies))
3 Configuration Units
10 m max.
50 m max. (with shielded cable)
10 m max.
100 m max. (with shielded cable)
100 m max.
500 m max.
3
*4
*5
*4
*5
3-25