Notes
5.3.16 Measuring the ionisation current
See subsection : "Measuring the ionisation current (fig. 35)"
on page 38.
5.3.17 Replacing the ionisation electrode
Remove the gas-air unit.
Loosen the plug-and-socket connection of the ionization
electrode.
Loosen screw (fig. 67, item 1) by a half-turn and slide
bar to remove.
Pull electrode to remove, and fit new unit.
Reassemble by following the above procedure in
reverse.
5.3.18 Checking KIM connections
Locate KIM on the side of the UBA bracket.
Check if 4 pin connector (fig. 68, item 1) is fitted and
secure.
NOTE
This is not a servicable part and any fault
identified with this component, contact
Buderus.
Buderus • http://www.buderus-domestic.co.uk
62
Installation and servicing instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 02/2006
Fig. 67 Replacing the ionisation electrode
Fig. 68 KIM connections