1 2
Vent Installation
•
In addition to the requirements below, follow the requirements provided with the vent.
Vertical Vent
Requirements
Use a roof flashing and storm collar
whenever passing through the roof
Use a ceiling firestop whenever passing through a
ceiling (or enclosure and at every floor penetration.
8"
by
8"
Horizontal Vent
Requirements
Minimum
8" wide
•
Slide the vent sections together and turn 1/4 turn until the sections lock in
place.
•
Screws are not required to secure the vent. However, three screws may be
used to secure vent sections together if desired.
•
High temperature sealant is recommended at the appliance starter section
connection (use high-temperature silicone or Mill-Pac®).
•
If disassembly is required, at time of re-assembly check to see if the vent
creates a tight fit. If it does not, apply high temperature sealant to the joints of
the affected sections.
•
Horizontal sections require a 1/4" rise every 12" of travel
•
Horizontal sections require non-combustible support every three feet (e.g.: plumbing tape)
Travis Industries
Installation
Minimum framing
for fire stop
Minimum framing
for fire stop
Minimum
11" tall
(for qualified installers only)
Use a firestop when passing through a wall. Make
sure there is a 2" clearance above the vent.
1 0 0 - 0 1 1 5 5
Vertical Termination
(part # 1291)
Combustible
Framing
0" Clearance on Vertical
Sections to combustible
surfaces.
0" Clearance
Combustible
Surfaces
2" Min.
1" Min.
4 0 4 0 9 0 3