Vent Terminal Clearances - Jøtul GF 500 DV IPI Installation And Operation Instructions Manual

Direct vent
Table of Contents

Advertisement

139636 GF 500 DV IPI 7/28/14
Horizontal Termination Clearance
Figure 24. Vent Terminal Clearances - ANSI Z21.88-2009, CSA 2.33-2009, and National Fuel Gas Code.
A = Clearance above grade, veranda, porch , deck, or balcony
: 12 inches (30 cm) minimum.
B = Clearance to window or door that may be opened:
**Min. 9 inches, U.S. / *12 inches (30 cm) CAN.
We recommend 12in. minimum to prevent condensation
on the window.
C = Clearance to permanently closed window:
**Min. 9 inches, U.S. / *12 inches (30 cm) CAN
We recommend 12 in. minimum to prevent condensation
on the window.
D = Vertical clearance to ventilated soffit located above the
terminal within a horizontal distance of 2 feet (60 cm)
from the center line of the terminal: 18 inches
(46 cm) minimum.
E = Clearance to unventilated soffit: 12 inches (30 cm)
minimum.
F = Clearance to outside corner: **Min. 9 inches, U.S. / *12
inches (30 cm) CAN. We strongly recommend 12 inches,
particularly where windy conditions pevail.
G = Clearance to inside corner: ** Min. 6 inches, U.S. / *12
inches (30 cm) CAN. We strongly recommend 12 inches,
particularly where windy conditions pevail.
H = *Not to be installed within 15 feet (4.5 m) above a me-
ter/regulator assembly within 3 feet (90 cm) horizontally
from the center line of the regulator.
I = Clearance to service regulator vent outlet:
3 feet (91 cm) minimum.
J = Clearance to nonmechanical air supply inlet to building
or the combustion air inlet to any other appliance:
12 inches (30 cm) minimum.
K = Clearance to a mechanical air supply inlet:
**Min. 3 feet (91 cm) above if within 10 feet horizontally,
U.S. / *6 feet (1.83 m) minimum / CAN
L =
Clearance above paved sidewalk or a paved driveway
1
located on public property: 7 feet (2.1 m) min.
16
V
Vent Terminal
X
Air Supply
Terminals Prohibited in this Area
M = Clearance under veranda, porch, deck, or balcony:
12 inches (30 cm) minimum.
N = Clearance to propane tank relief valve and filler connec-
tion***:
5 feet (1.52 m) minimum to tanks not filled on site
10 feet (3.05 m) minimum to tanks filled on site from bulk
truck.
* In accordance with CSA B149 Installation Codes.
** In accordance with the current ANSI Z223.1/NFFPA 54, National
Fuel Gas Code. Note: Local Codes and Regulations may require
different clearances.
A vent shall not terminate directly above a sidewalk or driveway
1
which is located between two single family dwellings and serves
both dwellings.
Only permitted if veranda, porch, deck, or balcony, is fully open
2
on a minimum of two sides beneath the floor.*
12 ”
305
mm
Figure 25. Termination Clearance to overhangs.
N
2
2 1/2”
64 mm
3”
76 mm