7
Boiler Installation
7.1.2.2 Installation of Aerocowl exhaust termination
(Part No. AT-4)
Follow guidelines in section 7.1.2.1 regarding the rel-
ative position of the exhaust and terminal.
Follow manufacturer's installation guidelines of the
AT-4.
This system consists of a 4" air intake hood, a 5" x 4" re-
ducer and a 26½" long, insulated Aerocowl exhaust ter-
mination. This termination has a zero clearance rating to
combustibles. Do not install the vacuum relief damper
("not needed").
Cut a 6" round opening in the outside wall at the se-
lected location. Apply silicone caulking to the back-
side of the outer face plate and secure it to the
outside wall.
Insert the Aerocowl termination from the outside up
to the outer wall stop. Ensure slope of ¼" per foot to
outside.
Slide inner plate on the termination up to the inside
wall, tighten the gear clamp and secure the inner
plate to the wall.
For Aerocowl AT-4 installations in Canada less than
7 ft. above ground, install a cage/screen over the ter-
mination to prevent injury from touching hot surfaces.
7.1.2.3 Installation of the concentric Fields termination (FT-4)
Follow manufacturer's installation guidelines of the
FT-4.
This system consists of a 5" x 4" reducer and a zero
clearance concentric combination intake/exhaust termi-
nation with a 4" provision for fresh air intake piping. Do
not install the vacuum relief damper ("not needed").
Cut a round 7" diameter opening in the outside wall
at the selected location.
Remove the 4" air intake collar from the termination
assembly.
Apply silicone caulking to the back side of the wall
face plate. Insert the concentric termination from the
outside.
Ensure slope of ¼" per foot to outside. Secure the
face plate to the outside wall.
Reinstall the 4" collar.
24
Fig. 17 Aerocowl exhaust termination (Part No. AT-4) and
separate air intake hood
Fig. 18 Combination air intake/exhaust termination (Part No.
FT-4)