Vitotronic 200 and 300-K Installation and Service

Checking Outputs Actuators and Sensors

The following relay outputs can be controlled subject to system design:
Display
"All actuators"
"Output 20"
"Output 52"
"Output 52"
"Output 52"
"DHW tank primary pump"
"DHW circ pump"
"Output 29"
"Central fault mess."
"Htg circ pump HC2"
"Mixing valve HC2"
"Mixing valve HC2"
"Htg circ pump HC3"
"Mixing valve HC3"
"Mixing valve HC3"
"EA1 output 1"
"AM1 output 1"
"AM1 output 2"
"Solar circuit pump"
"Solar circ pmp min"
"Solar circ pmp max"
"SM1 output 22"
Information regarding the mixing valve motor rotational
direction
The supply temperature must rise when the mixing valve
opens. If the temperature drops, either the motor is
turning in the wrong direction or the mixing valve set is
incorrectly fitted (observe the mixing valve installation
instructions).
Explanation
OFF
All actuators are switched off.
ON
Output 20 enabled.
Open
--
Neutr.
--
Close
--
ON
Output for circulation pump for DHW tank heating enabled.
ON
Output for DHW circulation pump enabled.
ON
Output 29 enabled.
ON
--
ON
Output for heating circuit pump enabled (heating circuit with mixing valve M2).
Open
Output "Mixing valve open" enabled (heating circuit with mixing valve M2).
Close
Output "Mixing valve close" enabled (heating circuit with mixing valve M2).
ON
Output for heating circuit pump enabled (heating circuit with mixing valve M3).
Open
Output "Mixing valve open" enabled (heating circuit with mixing valve M3).
Close
Output "Mixing valve open" enabled (heating circuit with mixing valve M3).
ON
Contact "P - S" on plug aBJ for extension EA1 closed.
ON
Output 1 enabled.
ON
Output 2 enabled.
ON
Output for solar circuit pump sF at solar control module, type SM1 enabled.
ON
Output for solar circuit pump sF at solar control module, type SM1 switched
to minimum speed.
ON
Output for solar circuit pump sF at solar control module, type SM1 switched
to maximum speed.
ON
Output sS at solar control module, type SM1 enabled.
Testing the relay – Vitotronic 300-K
1. Press OK and
simultaneously for approx. 4 sec.
2. "Actuator test"
Vitotronic 200 sensor check
1. Press OK and
until service comes up.
2. Use
to scroll to diagnosticsand select with OK.
3. Use
to scroll to generaland select with OK.
4. Use
to scroll to relevant sensorand press with
OK to view.
5. To exit press
.
Actuators
1. Press OK and
until service comes up.
2. Use
to scroll to actuator testand select with OK.
3. Use
to scroll to actuator to be tested and leave
highlight (actuator description will change from 'OFF'
to 'ON').
4. When complete to exit press
Note: The service level is automatically exited after 30
minutes.