External Demand Via 0-10V Input; External Blocking Via Switching Contact - Viessmann VITOTRONIC 200 Installation And Service Instructions Manual

Type ho1b & mw2b, digital boiler control unit & weather-compensated, digital cascade control unit
Table of Contents

Advertisement

Vitotronic 200 and 300-K Installation and Service
External Demand via 0 – 10V Input

External Blocking via Switching Contact

A Floating contact
B Plug avD of the control unit
Legend
A Floating contact
B Extension EA1
Demand for a system supply temperature set value.
Connection to input 0 -10V at extension EA1 (accessory).
See page 90.
0 - 1V
no default set supply temperature
1V
set value 50° F (10° C)
10V
set value 212° F (100° C)
Connection options:
Connection at plug avD
Extension EA1 (accessory, see page 90)
Connection
Note: 'Live' contacts lead to short circuits or phase
failure.
The external connection must be potential-free.
The burner is shut down when the contact is closed.
The boiler circuit pumps are switched off.
Note: The heating system has no frost protection while
it is blocked.
The boiler is not held at the lower boiler water
temperature.
Codes
Plug avD
Set coding address "99" in the "general"
group.
Extension EA1 Set "5D", "5E" or "5F" in the "General"
group to 3 or 4.
Installation Sequence