Code 2

"Solar" Group

Only in conjunction with solar control module, type SM1.
Coding
Coding in the factory set condition
00:8
The solar circuit pump starts when the
collector temperature exceeds the actual
DHW temperature by 8 K.
01:4
The solar circuit pump stops when the
differential between the collector temperature
and the actual DHW temperature is less than
4 K.
02:0
Solar circuit pump (multi stage) without speed
control by solar control module SM1.
03:10
The temperature differential between the
collector temperature and actual DHW
temperature is regulated to 10 K.
04:4
Controller amplification of the speed control
4%/K.
05:10
Minimum speed of the solar circuit pump
10% of the maximum speed.
06:75
Maximum speed of the solar circuit pump
75% of the maximum possible speed.
07:0
Interval function of the solar circuit pump
switched off.
08:60
The solar circuit pump stops when the actual
DHW temperature reaches the maximum
DHW tank temperature 140° F (60° C).
09:130
The solar circuit pump stops if the collector
temperature reaches 266 50 to 194° F
(130° C) (maximum collector temperature
to protect the system components).
0A:5
To protect the system components and heat
transfer medium:
The speed of the solar circuit pump is reduced
if the actual DHW tank temperature is 5 K
below the maximum DHW tank temperature.
0B:0
Frost protection function for solar circuit
switched off.
0C:1
nt monitoring switched on.
No flow rate captured in the solar circuit,
or flow rate too low.
0D:1
Night circulation monitoring switched on.
Unintentional flow rate is captured in the solar
circuit (e.g. at night).
56
Vitotronic 200 and 300-K Installation and Service
Possible change
00:2
The differential between the actual DHW
to
temperature and the start point for the solar
00:30
circuit pump can be adjusted from 2 to 30 K.
01:1
The differential between the actual DHW
to
temperature and the stop point for the solar
01:29
circuit pump can be adjusted from 1 to 29 K.
02:1
Solar circuit pump (multi stage) is speed-
controlled with wave pack control.
02:2
Solar circuit pump is speed-controlled with
PWM control.
03:5
The differential temperature control between
to
collector temperature and actual DHW
03:20
temperature can be adjusted from 5 to 20 K.
04:1
Controller amplification adjustable from
to
1 to 10%/K.
04:10
05:2
Minimum speed of the solar circuit pump
to
is adjustable from 2 to 100%.
05:100
06:1
Maximum speed of the solar circuit pump
to
is adjustable from 1 to 100%.
06:100
07:1
Interval function of the solar circuit pump
switched on.
To capture the collector temperature more
accurately, the solar circuit pump starts
for short cycles.
08:10
The maximum DHW tank temperature
to
can be adjusted from 50 to 194° F
08:90
(10 to 90° C).
09:20
The temperature can be adjusted from
to
68 to 392° F (20 to 200° C).
09:200
0A:0
Stagnation time reduction disabled.
0A:1
Value for stagnation time reduction adjustable
to
from 1 to 40 K.
0A:40
0B:1
Frost protection function for solar circuit
switched on (not required with Viessmann
heat transfer medium).
0C:0
nt monitoring switched off.
0D:0
Night circulation monitoring switched off.