Code 1

"Cascade" Group

Coding
Coding in the factory set condition
Number of boilers in cascade
35:4
4 boilers connected to the Vitotronic 300-K
Min. system supply temperature
36:0
Electronic minimum system supply
temperature limit set to 32° F (0° C)
Max. system supply temperature
37:80
Electronic maximum system supply
temperature limit set to 176° F (80° C)
Control type
3B:1
Stand-alone parallel boiler connection with
supply temperature sensor
Control strategy
3C:0
Condensing strategy (see page 78)

"DHW" Group

Coding
Coding in the factory set condition
Set DHW temperature reheating suppression
67:40
For solar DHW heating:
Set DHW temperature 104° F (40° C).
Reheating is suppressed above the selected
set temperature (DHW heating blocked by the
boiler).
Enable DHW circulation pump
73:0
DHW circulation pump: "ON" according to time
program
36
Vitotronic 200 and 300-K Installation and Service
Possible change
35:1
1 to 8 boilers connected to the Vitotronic 300-K
to
35:8
36:1
Electronic minimum system supply temperature
to
limit adjustable from 32 to 260° F
36:127
(0 to 127° C)
37:20
Electronic maximum system supply temperature
to
limit adjustable from 68 to 260° F
37:127
(20 to 127° C)
3B:0
Stand-alone parallel boiler connection without
supply temperature sensor
3C:1
Conventional boiler strategy 1 (see page 79)
3C:2
Conventional boiler strategy 2 (see page 79)
Possible change
67:0
Set DHW temperature adjustable from 32 to
to
203° F (0 to 95° C)
67:95
(limited by boiler-specific parameters)
73:1
"ON" from once per hour for 5 min. up to
to
6 times per hour for 5 min. during the time
73:6
program
73:7
Constantly "ON"