Vitotronic 200 and 300-K Installation and Service

"General" Group

Coding
Coding in the factory set condition
System design
00:1
System version 1:
One heating circuit without mixing valve A1
(heating circuit 1), without DHW heating
Value address
System version
00: ...
2
1
3
2,3
4
2,3
5
2,3,4
6
2,3,4
7
5
8
5
9
5
10
5
Coding in the factory set condition
Participant number
77:5
LON participant number
Detached house/apartment building
7F:1
Detached house
Lock out controls
8F:0
All control elements active
Set supply temperature for external demand adjustable from
9B:70
Set supply temperature for external
demand 158° F (70° C)
Description
One heating circuit without mixing valve A1 (heating circuit 1),
with DHW heating (code is adjusted automatically)
One heating circuit with mixing valve M2 (heating circuit 2),
without DHW heating
One heating circuit with mixing valve M2 (heating circuit 2),
with DHW heating
One heating circuit without mixing valve A1 (heating circuit 1) and one heating
circuit with mixing valve M2 (heating circuit 2),
without DHW heating (code is adjusted automatically)
One heating circuit without mixing valve A1 (heating circuit 1) and one heating
circuit with mixing valve M2 (heating circuit 2),
with DHW heating (code is adjusted automatically)
One heating circuit with mixing valve M2 (heating circuit 2) and one heating circuit
with mixing valve M3 (heating circuit 3), without DHW heating
One heating circuit with mixing valve M2 (heating circuit 2) and one heating circuit
with mixing valve M3 (heating circuit 3), with DHW heating
One heating circuit without mixing valve A1 (heating circuit 1), one heating circuit
with mixing valve M2 (heating circuit 2) and one heating circuit
with mixing valve M3 (heating circuit 3), without DHW heating (code is adjusted
automatically)
One heating circuit without mixing valve A1 (heating circuit 1), one heating circuit
with mixing valve M2 (heating circuit 2) and one heating circuit
with mixing valve M3 (heating circuit 3), with DHW heating (code is adjusted
automatically)
Possible change
77:2
to
77:99
7F:0
8F:1
8F:2
9B:0
to
9:127
Possible change
00:2
For system schemes, see the following table:
to
00:10
LON participant number, adjustable from 1 to 99:
1 - 4 = Boiler
5 = Cascade
10 - 98 = Vitotronic 200-H
99 = Vitocom
Note: Allocate each number only once.
Apartment building
Separate adjustment of holiday program and time
program for DHW heating possible
All control elements locked out
Only standard settings can be controlled
Set supply temperature for external demand adjustable
from 32 to 260° F (0 to 127° C) (limited by boiler-
specific parameters)
Code 1