Calling Up Coding Level 2 - Vitotronic 200 - Viessmann VITOTRONIC 200 Installation And Service Instructions Manual

Type ho1b & mw2b, digital boiler control unit & weather-compensated, digital cascade control unit
Table of Contents

Advertisement

Code 2
Calling up Coding Level 2 – Vitotronic 200
42
Vitotronic 200 and 300-K Installation and Service
Prior to coding the Vitotronic 200, ensure the boiler is
in cascade mode. Refer to page 10.
For the Vitotronic 200, see boiler Service
Instructions
1. Press
and OK for approximately 4 seconds.
2. Use
to scroll to serviceand select with OK.
3. Use
to scroll to service functionsand select
with OK.
3. Use
to scroll to multi-boiler systemand select
with OK.
4. When complete to exit press
Note: At coding level 2, all codes are accessible,
including the codes at coding level 1.
Codes that have not been assigned due to the
heating system equipment level or the setting of
other codes are not displayed.
1. Press OK and
simultaneously for approximately
4 seconds.
2. Press OK and
simultaneously for approximately
4 seconds.
3. "Coding level 2"
4. Select group of required coding address:
- "General"
- "Boiler"
5. Select coding address.
6. Select value according to the following tables and
confirm with "OK".
7. If you want to reset all codes to their factory setting:
Select "Standard setting" in "Coding level 2".
Note: This also resets codes at coding level 1.
.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitotronic 300-k

Table of Contents