External Connections; Grounding Instructions; Power - ESI -1000 Installation Manual

Communications servers
Hide thumbs Also See for ESI-1000:
Table of Contents

Advertisement

ESI Communications Servers Hardware Installation Manual

External connections

Grounding instructions

System grounding (supplemental ground) is as follows:
• The conductor wires can be no smaller than the ungrounded branch-circuit supply conductors (usually 16-
gauge or higher).
• Acceptable wire: bare or covered with green (or green-and-yellow-striped) jacket.
• Conductors (and power receptacles) shall connect to earth ground at the service equipment (usually a cold
water pipe or copper ground rod).
• The supplemental ground must: be used regardless of power cord ground, be connected to the ground lug
on the bottom of the cabinet, and retain ground connection when the power supply module is unplugged.
• Connect the grounding lugs of all units to system ground
Note: ESI Communications Server lines are protected against a 10 KV surge only if the earth ground procedures
described above are followed.

Power

Each cabinet requires a 110 VAC outlet (if possible, a dedicated outlet). Use only the Class-2 power supply
module provided. A clean, isolated power source in conjunction with a UPS is STRONGLY recommended.
The following table shows the power consumption of each ESI Communications Server when fully loaded:
System
ESI-1000
ESI-600
ESI-200
ESI-100
ESI-50
If AC power is interrupted, the system will drop all connections. When power is restored, the system will resume
normal operation in approximately five minutes, having retained its full programming and clock setting.
UPS
For system protection and to maintain uninterrupted operation, an uninterruptible power supply is
STRONGLY recommended. Here are the recommended UPS ratings for each system:
Refer to the particular UPS unit's specifications to determine expected backup duration during a power outage.
Note: The remaining information under "UPS" comes from Technical Update #216.
Most people have heard about UPSs, but seem to think that there is just one kind of device that goes by that
name. In fact, there are several different major designs in use by today's major UPS manufacturers. These
makers share much of the blame for confusing UPSs' end users by, far too often, lumping different designs
under the "UPS" name.
(Continued)
Cabinets (Base and Expansion)
in fully loaded system
6
4
2
2
2
System
Recommended UPS minimum rating
PER INSTALLED CABINET (in VA)
ESI-1000
ESI-600
ESI-200
ESI-100
ESI-50
Power consumption
(in watts)
1,080
720
360
125
72
230
230
230
125
125
I.1
External connections

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Esi-600Esi-200Esi-100Esi-50