CTH2-Series S

CLEARANCES TO COMBUSTIBLES

NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.
3. "-" indicates an unapproved application. Roberts-Gordon prohibits the installation of
this heater for all unapproved applications.

Standard Reflector

A
C
B
D

One Side Reflector

A
C
B
D

Two Side Reflectors

A
C
B
D
© 2004 Roberts-Gordon
S
UBMITTAL
HEET
Model
CTH2-40
CTH2-60
CTH2-80
CTH2-100
CTH2-125
CTH2-150
CTH2-175
Model
CTH2-40
CTH2-60
CTH2-80
CTH2-100
CTH2-125
CTH2-150
CTH2-175
Model
CTH2-40
CTH2-60
CTH2-80
CTH2-100
CTH2-125
CTH2-150
CTH2-175
APPLICATIONS, ENGINEERING AND DETAILED GUIDANCE ON SYSTEMS DESIGN, INSTALLATION AND PRODUCT PERFORMANCE IS AVAILABLE UPON REQUEST. ROBERTS GORDON
INSTALLED ONLY IN ACCORDANCE WITH LOCAL LAWS, CODES AND REGULATIONS, AND ONLY BY A CONTRACTOR QUALIFIED IN THE INSTALLATION AND SERVICE OF GAS-FIRED HEATING EQUIPMENT.
(inches)
A
B
C
6
27
53
27
6
35
63
35
6
38
66
38
6
40
71
40
6
46
77
46
6
50
80
50
8
52
82
52
(inches)
A
B
C
6
9
53
44
6
9
63
47
6
9
70
54
6
9
77
59
6
9
83
65
6
9
86
69
8
9
88
73
(inches)
A
B
C
6
15
53
15
6
23
66
23
6
25
72
25
6
27
78
27
6
32
84
32
6
35
88
35
8
40
91
40
(centimeters)
D
A
B
16
69
135
16
89
161
16
97
168
16
102
181
16
117
196
16
127
204
21
133
209
(centimeters)
D
A
B
16
23
135
16
23
161
16
23
178
16
23
196
16
23
211
16
23
219
21
23
224
(centimeters)
D
A
B
16
39
135
16
59
168
16
64
183
16
69
199
16
82
214
16
89
224
21
102
232
C
D
69
89
97
102
117
127
133
C
D
112
120
138
150
166
176
186
C
D
39
59
64
69
82
89
102
®
PRODUCTS ARE TO BE