Reflector, U-Clip And Reflector Support Installation - Roberts Gorden CTH2 Series Installation, Operation And Service Manual

Low-intensity systems heating systems
Table of Contents

Advertisement

ROBERTS GORDON
®
CTH2-Series S

Reflector, U-Clip and Reflector Support Installation

The pictorial drawings of the heater construction in
Section are schematic only and provide a general
guideline of where hangers, reflector supports and
U-clips are to be installed.
1. The first reflector after the burner must be affixed in
the middle of the reflector with a reflector support and
tight screws.
Reflector
End Cap
U-Clips
Overlap must be a
minimum of 6" (16 cm)
2. The overlap at the first and second reflector is a slip overlap.
Thereafter, every third reflector joint is a slip overlap. A slip
overlap is achieved by either:
a.) both reflectors lay inside a hanger.
(no reflector support needed).
b.) using a reflector support with
loose screws at the reflector
overlap.
3. The remaining reflector overlaps require a non-slip
overlap connection. To affix the reflectors together in
a non-slip overlap either:
a.) use reflector support and tight screws.
b.) if both reflectors lay inside a hanger, u-clips or
sheet metal screws may be used.
This section of three reflectors joined together must
be affixed to the tube with at least one reflector support
with tight screws.
Description
Reflector Support Package
Wire Form
Reflector Support Strap
Screw #8 x 3/4
U-Clip Package
Reflector End Cap
© 2004 Roberts-Gordon
S
UBMITTAL
HEET
First Reflector
6"
(16 cm)
Part Number
03050010
91908004
03050000
94320812
91107720
027508XX
APPLICATIONS, ENGINEERING AND DETAILED GUIDANCE ON SYSTEMS DESIGN, INSTALLATION AND PRODUCT PERFORMANCE IS AVAILABLE UPON REQUEST. ROBERTS GORDON
INSTALLED ONLY IN ACCORDANCE WITH LOCAL LAWS, CODES AND REGULATIONS, AND ONLY BY A CONTRACTOR QUALIFIED IN THE INSTALLATION AND SERVICE OF GAS-FIRED HEATING EQUIPMENT.
To ensure proper expansion and contraction move-
ment of the reflectors, a combination of U-clips and
reflector supports are used. The positioning of reflec-
tor supports and U-clips depend on the individual
installation. The following rules must be observed.
Option B
Slip Overlap
Option A
Slip Overlap
Option A
Non-Slip Overlap
Option B
Non-Slip Overlap
Tight
Sheet Metal
Screw
Wire Form
Reflector Support
Strap
Reflector
Reflector
Support
Loose screws
loosened 1/16"
(2 mm) to allow
slippage.
Reflector
Tight
screws
U-Clip
(2 clips per
non-slip overlap
inside a hanger)
®
PRODUCTS ARE TO BE