Test Options; Time Programs - Honeywell XI581AH User Manual

Buswide operator interface
Table of Contents

Advertisement

XI581/2 BUSWIDE OPERATOR INTERFACE
Store Template

Test Options

Time Programs

Blank
Cut-off string
Stop at the desired character. Repeat for each character you want to change.
RESULT: The template displays as changed. For example:
Modify Template
Store Template
7. Press Enter to highlight the string. Use the arrow keys to move to and highlight
Store Template. Press Enter (↵) to complete the selection.
Or, if you do not wish to save the changes, exit by pressing Cancel (C) before
selecting 'Store Template'. If you already stored the template, use the 'Delete a
Template' function.
RESULT: The changed template is added to the template list shown on the
Modify Template
8. Select another template and press Enter (↵) to modify it. Or, press Cancel (C) to
return to the 'Data Points' screen.
Purpose
To checkout or troubleshoot the system by manually setting outputs and verifying
inputs. See section "Default Data Points" (page 41).
General
Excel controllers allow equipment control based on time of day. For example, you
can set HVAC equipment start and stop times. Time programs implement this
control strategy. Each controller can have a maximum of 20 time programs.
The following figure illustrates a time program that controls lighting in a school.
Each time program specifies one weekly program. This weekly program schedules
the normal daily activity of the system by specifying which daily programs an Excel
controller should use for each day of a normal week (Sunday through Saturday).
Daily programs list points and point actions for the Excel controller to execute. The
points and point actions are called switch points. Daily programs with their switch
points are assigned to weekly programs to provide for automatic operations on
scheduled days.
An annual program applies the weekly program to each week of the year. The
controller operates according to the annual program.
To accommodate special events (such as unplanned conferences and after-hour
assemblies), a TODAY program can override a point action or switch point
Delete the selected character after you press the right arrow.
Or, replace with the original character if you press Enter.
If you select two asterisks in a row, **, all characters to the
right are automatically cleared.
FLOOR1?
display. Example:
FLOOR7*
FLOOR1?
75