XI581/2 BUSWIDE OPERATOR INTERFACE

Application Selection

Select Application Program
1.
CARE V2.02.00 or later:
The maximum application size is 128 Kbytes (128 Kbytes flash
memory). Enter the application size calculated by CARE.
2.
CARE versions before V2.02.00 without modem:
The maximum application size calculated by the old CARE is
113 Kbytes because the complete application including RACL runs
from out of the RAM. The controller will not run if the application is
bigger. You need to use CARE at least V2.02.00 if your applications
require more than 113 Kbytes.
Applications bigger than 113 Kbytes without modem will not run
out of flash memory after firmware download of OS V2.03.01 if
they were done with CARE versions before V2.02.00.
3.
CARE versions before V2.02.00 with modem:
The maximum application size calculated by the old CARE is
100 Kbytes. The controller will not run if the application is bigger. For
the calculation of the trend buffer, you need to enter 28 Kbytes plus
the application size calculated by the old CARE version, e.g. CARE
V2.02.xx calculated 98 Kbytes, thus you will enter 126 Kbytes
(98 Kbytes + 28 Kbytes) on the MMI of the controller.
We strongly recommend using CARE V2.02.00 or later if you use
modem communication. This will allow for applications with up to
128 Kbytes (128 Kbytes flash memory).
Applications bigger than 100 Kbytes with modem will not run out
of flash memory after firmware download of OS V2.03.01 if they
were done with CARE versions before V2.02.00.
Steps 1 and 2 of the Start-up Sequence bring up the following screen:
01.01.1999
14:45
Modem
Applic. Mem. Size: 128 KB
Controller Setup
Application Selection
Data Point Wiring Check
3. Use the arrow keys to move to and highlight Application Selection and press
Enter (↵) to complete the selection.
RESULT: The first 'Application Selection' screen appears.
Application Selection
Select FLASH Application
Request Download
NOTE:
The 'Select FLASH Application' option appears only if there is at least
one application loaded in Flash EPROM.
4. Use the arrow keys to move to and highlight Select FLASH Application and
press Enter (↵) to complete the selection.
39
EVERYDAY OPERATIONS
Controller: 23
Part: inactive