Honeywell XI581AH User Manual page 63

Buswide operator interface
Table of Contents

Advertisement

XI581/2 BUSWIDE OPERATOR INTERFACE
Access Level
Select Data Point from Main Menu
Select Point Suppression Option
Select a Point
You must have access level 3 to perform this task.
1. At the Main Menu, use the arrow keys to move to and highlight Data Points.
Press Enter (↵) to complete the selection.
RESULT: The 'Data Points' screen appears. User Address is highlighted by
default.
Data Points
User Address
Manual Operation
Accumul. Runtime
Type Selection
Points in Trend
2. Use the arrow keys to move to and highlight Suppress Alarm and then press
Enter (↵) to complete the selection.
RESULT: The display window lists suppressed points.
Suppress Alarm
Exhaust_fan
Hall_main_lights
Main_water_meter
Conf_room_temp
NOTE:
All suppressed points may not be able to appear in the display
window at the same time.
3. Use the arrow keys to move to and highlight the point for which you want to
unsuppress alarm conditions. Press Enter (↵) to complete the selection.
NOTE:
Additional user-defined text may appear on the line beneath the user
address.
RESULT: The window allows you to unsuppress the point so it can report
alarm information.
NOTE:
Regardless as to whether an alarm is suppressed or not, whenever
the alarm occurs, it is written to the alarm buffer. The difference is
that if the alarm is suppressed, it does not display on an operator
interface.
Suppress Alarm
Hall main lights
Suppress Alarm: YES
4. Use the arrow keys to move to and highlight the Suppress Alarm field. Press
Enter (↵) to complete the selection.
RESULT: The entry in the Suppress Alarm field starts blinking and is no longer
highlighted.
5. Press the plus or minus keys to change 'Suppress Alarm' between 'Yes' and
'No'. Press Enter (↵) to complete the selection.
RESULT: The entry in the Suppress Alarm field stops blinking but is still high-
lighted.
6. Use the arrow keys to move to and highlight Back. Press Enter (↵).
RESULT: The 'Data Points' screen redisplays.
59
ALPHABETIC REFERENCE
Suppress Alarm
Add Template
Delete Template
Modify Template
Template Search
L L L L
I
1
I
M
Back
EN2B-0126 (74-3554-8)