24-Hr Auxiliary Input Wiring (Pgm2); Keyswitch Zone Wiring; Gsm1000 Supervisory (24 Hour Supervisory); Gsm1000 Answer - DSC Power 832 Installation Manual

Security system
Hide thumbs Also See for Power 832:
Table of Contents

Advertisement

G
E
T
If PGM2 is programmed for 2-wire smoke support, the connector CON1 on the main board must be re-
moved.
2.9.6

24-Hr Auxiliary Input Wiring (PGM2)

If PGM2 has been programmed for 24-hour operation, the zone must be wired according to the following diagram:
If PGM2 is programmed for 24-Hr auxiliary input support, the connector CON1 on the main board must
be removed.
2.9.7

Keyswitch Zone Wiring

2.9.8

GSM1000 Supervisory (24 Hour Supervisory)

2.9.9

GSM1000 Answer

The GSM1000 Answer zone is only required for downloading to the panel via the GSM1000.
When using the GSM1000, busy tone detection must not be used.
Keypad zones cannot be used for 24 Hour Supervisory or GSM1000 Answer.
2.10

Keypad Zones

Keypads with zone inputs can be connected to devices such as door contacts. This eliminates the need to run wires
back to the control panel for every device.
To install the keypad, open the keypad plastic by removing the screw at the bottom of the unit. Locate the five terminals on
the keypad circuit board. Connect the four Keybus wires from the control panel: the red wire to R, the black to B, the yellow
to Y and the green to G.
To connect the zone, run one wire to the Z terminal and the other to B. For powered devices, use red and black to supply
power to the device. Run the red wire to the R (positive) terminal and the black wire to the B (negative) terminal.
When using end of line supervision, connect the zone according to one of the configurations outlined in Section 2.8 "Zone
Wiring." End of line resistors must be placed on the device end of the loop, not at the keypad.
T
I
N
G
When using the GSM1000 cellular communicator, any main board zone may be
configured for GSM1000 supervision. Program this zone as zone type [09], 24-
Hour Supervisory in section [001].
With a 24-Hour Supervisory zone, if the GSM1000 experiences a trouble, the zone will
be violated, causing the panel to report the event to the central station. This type of
zone always requires a single EOL resistor (5600Ω).
Wire this zone according to the diagram.
If the GSM1000 cellular communicator is being used a zone may be configured
for GSM1000 Answer to allow downloading to be performed in the event of
phone line failure.
When the GSM1000 receives a phone call it will activate the RING terminal on the
GSM1000 circuit board. This terminal can be used to violate a zone programmed as
GSM1000 Answer (See Section 5.1 "Zone Definitions") , causing the panel to seize the
phone line and begin communication with the downloading computer.
The zone programmed as GSM1000 Answer ALWAYS requires a single EOL resistor
(5600Ω) and must be wired according to this diagram.
S
T
A
Zones may be programmed to be used as keyswitch
arming zones and must be wired according to the
following diagrams:
For a complete description of how keyswitch zones
operate, see Section 5.1 "Zone Definitions".
11
R
T
E
D