Gas Connection; Gas Pipe Pressure Testing - Regency ULTIMATE U38 Installation Manual

Ultimate u38 freestanding gas stove
Hide thumbs Also See for ULTIMATE U38:
Table of Contents

Advertisement

GAS CONNECTION

The gas line can be rigid pipe, or to make instal-
lation easier, use a listed fl exible connector if
allowed by local codes. Copper may also be
used if approved by local codes.
The gas connection at the valve is 3/8" NPT.
For minimum and maximum supply pressure
see the System Data Table.
System Data
U38-1 with 40,000 BTU
U38-NG1: For 0 to 2000 feet altitude
U38-LP1: For 0 to 4500 feet alttitude
Burner Inlet Orifi ce Sizes:
Natural Gas
Burner
#31
Max. Input
Natural Gas
40,000 Btu/h
Propane
38,000 Btu/h
Min. Input
Natural Gas
22,000 Btu/h
Propane
20,000 Btu/h
Supply Pressure
Natural Gas
min. 5" w.c.
Propane
min. 12" w.c.
Manifold Pressure
Natural Gas
3.8"
Propane
11"
Electrical: 120 V. 1.13A 60Hz.
Circulation: Variable speed fan, 125/75
CFM.
Log Set: Ceramic fi ber, 7 per set.
System Data:
HIGH ELEVATION - U38-NG1
For 2,000 - 4,500 feet altitude
Burner Inlet Orifi ce Sizes:
Natural Gas
Burner
Max. Input Rating 36,000 Btu/h
Min. Input Rating 19,000 Btu/h
®
Regency
U38-1 ULTIMATE Freestanding Gas Stove
U38-1 Converted to 30,000 Btu
For 0 to 4500 feet altitude
Burner Inlet Orifi ce Sizes:
Burner
Max. Input
Natural Gas
Propane
Min. Input
Natural Gas
Propane
Supply Pressure
Natural Gas
Propane
Propane
#50
Manifold Pressure
Natural Gas
Propane
Electrical: 120 V. 1.13A 60Hz.
Circulation: Variable speed fan, 125/75
CFM.
GAS PIPE PRESSURE
+/- 0.2" w.c.
The appliance must be isolated from the gas
+/- 0.2" w.c.
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig. (3.45
kPa). Disconnect piping from valve at pressures
over 1/2 psig (14" w.c.).
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note:
To properly check gas pressure,
#33
both inlet and manifold pressures
should be checked using the valve
pressure ports on the valve.
1) Make sure the valve is in the "OFF" posi-
tion.
2) Loosen the "IN" (# 7) and/or "OUT" (# 6)
pressure tap(s), turning counterclockwise
with a 1/8" wide fl at screwdriver.
3) Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" ID hose.
System Data
Natural Gas
Propane
#37
#52
30,000 Btu/h
30,000 Btu/h
15,000 Btu/h
15,000 Btu/h
min. 5" w.c.
min. 12" w.c.
3.8"
+/- 0.2" w.c.
11"
+/- 0.2" w.c.
TESTING
INSTALLATION
4) Light the pilot and turn the valve to "ON"
position.
5) The pressure check should be carried out
with the unit burning and the setting should
be within the limits specifi ed on the safety
label.
6) When fi nished reading manometer, turn
off the gas valve, disconnect the hose and
tighten the screw (clockwise) with a 1/8" fl at
screwdriver. Screw should be snug, but do
not over tighten.
S.I.T. Valve Description
1) Gas on/off knob
2) Manual high/low adjustment
3) Pilot Adjustment
4) Thermocouple Connection
5) Main Operator
6) Outlet Pressure Tap
7) Inlet Pressure Tap
8) Pilot Outlet
9) Main Gas Outlet
10) Flange Securing Screw Holes
11) Alternative TC Connection Point
12) Thermoelectric Unit
13) Additional Valve Mounting Hole
9