Making Control Connections

MicroTech II™ Unit Mounted DDC Control
Components – Models AVS, AVV, and AVR
1
MicroTech II Unit Ventilator Controller (UVC): (Located
Beneath the Local User Interface Panel). Factory mounted and
run tested, microprocessor-based DDC control device capable
of complete Standalone unit control, Master/Servant control or
incorporated into a building-wide network using an optional plug-in
communication module. The UVC contains a microprocessor that
is preprogrammed with the application code required to operate the
unit. The UVC supports up to 6 analog inputs, 12 binary inputs,
and 9 binary outputs. The UVC EXP I/O board supports up to 4
additional analog inputs and 8 additional binary outputs. Master/
Servant units have the controller factory configured and installed
for a local peer-to-peer network between these units (network
wiring between these units needs to be field installed). Optional
network communication is provided via plug-in communication
modules that connect directly to the UVC.
2
Communication Module (optional): Plug-in network
communication module that is attached to the UVC via a 12-
pin header and 4 locking standoffs. Available communication
modules:
Building Automation and Control Network (BACnet
Master Servant/Token Passing (MS/TP) - Allows the UVC to
inter-operate with systems that use the BACnet (MS/TP) protocol
with a conformance level of 3. Meets the requirements of ANSI/
ASHRAE 135-1995 standard for BACnet systems.
LonWorks
®
compliant Space Comfort Controller (SCC)
– Supports the LonWorks SCC profile number 8500_10.
®
Metasys N2
Open – Provides N2 Open network
communication capability to the UVC.
3
Local User Interface (LUI): (see fig. 93) The LUI provides a unit
mounted interface which indicates the current unit operating state
and can be used to adjust the unit ventilator operating parameters
(operating mode, temperature set points, fan speed and occupancy
mode). The LUI features a 2-digit display, 7 keys (1 key is hidden),
and 9 individual LED indicators. See "Local User Interface" for
further details.
4
Tenant Override Switch (see fig. 94) – Provides a momentary
contact closure that causes the unit to enter the "tenant override"
operating mode for a set time period (default = 120 minutes).
Figure 92 - MicroTech II Sensor and
Component Locations (Front View)
12
11
17
IM 817-4
19
15
18
5
Time Clock (TC) (optional on standalone units only) (see fig.
94) – Factory mounted 7 day/24 hour, digital time clock with up
to twenty (20) programs to sequence the unit ventilator through
occupied and unoccupied modes in accordance with a user
programmed time schedule.
6
External Signal Connection Plugs: Three (3) multi-pin
plugs are factory provided and pre-wired with short wire
whips that are capped (they must remain capped if not used).
Provided for field wiring of :
Remote Wall Mounted Temperature Sensor
(optional accessory).
External Input Signals (by others): unoccupied, remote
shutdown, ventilation lockout, dew point/humidity (night
time operation), or exhaust interlock signals
External Output Options (by others): lights on/off,
fault indication signal, exhaust fan on/off or auxiliary heat
signal.
7
Electric Connection Box: Contains the motor speed transformer.
Refer to the unit wiring diagram for specifics.
8
Unit Main Power "On-Off" Switch: (SW1) Disconnects the
main power to the unit for servicing or when the unit is to be shut
down for an extended period of time.
9
Fuse(s) - Fan motor and controls have the hot line(s) protected
by factory installed cartridge type fuse(s).
®
)
10 Control Transformer - 75 VA 24-volt NEC Class 2 transformer for
24 volt power supply. (Located behind the motor transformer).
11
Outdoor Air/Return Air Damper Actuator - (A1) Direct coupled,
floating point (tristate) actuator that spring returns the outdoor air
damper to the closed position upon a loss of power.
12 Face and Bypass Damper Actuator - (A2) Direct coupled, floating
point (tristate) actuator that is non-spring returned (Model AVS
only).
13 Hydronic Coil Low Air Temperature Limit (T6 freezestat)
– Factory installed on all units with hydronic (water) coils. The
T6 freezestat cuts out at 38
o
o
at 45
F (+/- 3
F).
14 Low Refrigerant Temperature Sensor (S4) - The S4 sensor is
provided on all units with a direct expansion (DX) cooling coil.
It is located on the right hand side of the coil "u-bend".
Not all external signal options can be used simultaneously and
may not be available on all software models. Refer to the "UVC
Input and Output Tables" in IM 739 for available options.
16
o
F (+/- 3
o
F) and automatically resets
NOTICE
6
13
14