Clearances; Roof Curb Post-Installation Checks; Roof Top Duct Connections - Daikin DCC Series Installation Instructions Manual

Light commercial packaged heating and cooling unit 7.5 to 12.5 to
Table of Contents

Advertisement

CLEARANCES

48"
UNIT CLEARANCES
*In situations that have multiple units, a 48" minimum clearance
is required between the condenser coils.
Maintain an adequate clearance around the unit for safety,
service, maintenance, and proper unit operation. Leave a
clearance of 48" on all sides of the unit for possible compres-
sor removal or service access, and to ensure proper ventila-
tion and condenser airflow. Do not install the unit beneath any
obstruction. Install the unit away from all building exhausts to
inhibit ingestion of exhaust air into the unit's fresh-air intake.
Roof Curb Installation
48"
48"
48"
INSULATED
PANELS

ROOF CURB POST-INSTALLATION CHECKS

After installation, check the top of the curb, duct connection
frame and duct flanges to make sure gasket has been ap-
plied properly. Gasket should be firmly applied to the top
of the curb perimeter, duct flanges and any exposed duct
connection frame. If gasket is loose, re-apply using strong
weather resistant adhesive.
P
rotrusion
Inspect curb to ensure that none of the utility services (elec-
tric) routed through the curb protrude above the curb.
I
,
F PROTRUSIONS EXIST
DO NO ATTEMPT TO SET UNIT ON CURB

ROOF TOP DUCT CONNECTIONS

Install all duct connections on the unit before placing the
unit on rooftop.
H
D
OrizOntal
isCHarge
To convert to horizontal discharge, remove the covers over the
horizontal duct connections (save washered screws). Refer to
IOD-7006 included in the literature pack for installing hori-
zontal duct covers to the downflow duct connections.
Flexible duct connectors between the unit and ducts are rec-
ommended. Insulate and weatherproof all external ductwork
and joints as required and in accordance with local codes.
REMOVE
COVERS
28 3/8"
13 7/8"
SUPPLY
6 1/4"
HORIZONTAL DISCHARGE DUCT CONNECTIONS
5
CAUTION
12 5/8"
5 7/8"
7 3/8"
RETURN
36 3/8"
.

Hide quick links: