Servicing; Checking Voltage; Checking Wiring; Checking Thermostat And Wiring - Daikin DP14UM Service Instructions Manual

Seer ultra-low nox gas electric
Table of Contents

Advertisement

SERVICING

S-1 Checking Voltage
High Voltage!
Disconnect all power before servicing or
installing. Multiple power sources may be
present. Failure to do so may cause property
damage, personal injury or death.
1. Remove doors, control panel cover, etc. from unit
being tested.
With power ON:
Line voltage now present
2. Using a voltmeter, measure the voltage across
terminals L1 and L2 of the contactor for single phase
units, and L3, for 3 phase units.
3. No reading - indicates open wiring, open fuse(s) no
power or etc. from unit to fused disconnect service.
Repair as needed.
4. If incoming voltage is within the range listed in the
chart below, energize the unit.
5. Using a voltmeter, measure the voltage with the
unit starting and operating to determine if voltage is
within the range listed in the chart below.
6. If the voltage falls below the minimum voltage, check
the line wire size. Long runs of undersized wire can
cause low voltage. If the wire size is adequate, notify
the local power company regarding either low or high
voltage.
Unit Supply Voltage
Voltage
208/230
S-2 Checking Wiring
High Voltage!
Disconnect all power before servicing or
installing. Multiple power sources may be
present. Failure to do so may cause property
damage, personal injury or death.
WARNING
WARNING
Min.
Max.
198
253
WARNING
1. Check wiring visually for signs of overheating,
damaged insulation and loose connections.
2. Use an ohmmeter to check continuity of any
suspected open wires.
3. If any wires must be replaced, replace with
comparable gauge and insulation thickness.
S-3 Checking Thermostat and Wiring
Thermostat Wiring: The maximum wire length for 18 AWG
thermostat wire is 100 feet.
Line voltage now present
With power ON, thermostat calling for cooling
1. Use a voltmeter to check for 24 volts at thermostat
wires C and Y in the condensing unit control panel.
2. No voltage indicates trouble in the thermostat, wiring
or external transformer source.
3. Check the continuity of the thermostat and wiring.
Repair or replace as necessary.
Indoor Blower Motor
With power ON:
Line voltage now present
1. Set fan selector switch at thermostat to "ON"
position.
2. With voltmeter, check for 24 volts at wires C and G.
3. No voltage indicates the trouble is in the thermostat
or wiring.
4. Check the continuity of the thermostat and wiring.
Repair or replace as necessary.
S-4 Checking Transformer and Control Circuit
High Voltage!
Disconnect all power before servicing or
installing. Multiple power sources may be
present. Failure to do so may cause property
damage, personal injury or death.
WARNING
WARNING
WARNING