CGi
GAS-FIRED WATER BOILER — SERIES 3 —
10a
Service and maintenance — schedule
Table 8 Service and maintenance schedules
(see following pages for instructions)
Inspect:
Service:
Start-up:
Check/test:
Review:
44
VERIFY PROPER OPERATION AFTER SERVICING
Service technician
• Reported problems
• Boiler area
• Air openings
• Flue gas vent system (and air piping)
• Pilot and main burner flames
• Water piping
• Boiler heating surfaces
• Burners, base and inlet air box
• Condensate drain system
• Inducer motor
• Oiled-bearing circulators
• Temperature sensor
• Perform start-up per manual
• Gas piping
• Cold fill and operating pressures
• Air vents and air elimination
• Limit controls and cutoffs
• Expansion tank
• Boiler relief valve
• Review with owner

Service and maintenance

Follow the
ponent literature shipped with the boiler. Failure to perform the service and maintenance
could result in damage to the boiler or system. Failure to follow the directions in this manual
and component literature could result in severe personal injury, death or substantial property
damage.
Boiler Manual
Owner maintenance
(see CGi User's Information Manual for instructions)
• Check boiler area
• Check air openings
Daily
• Check boiler pressure
• Check boiler interior piping
• Check venting system
• Check air vents
Monthly
• Check boiler relief valve
• Check condensate drain system
• Check automatic air vents (if
Periodically
• Test low water cutoff (if used)
• Oil inducer motor
Every 6 months
• Operate relief valve
End of season
• Shut down procedure
procedures given throughout this manual and in com-
temperature gauge
used)
Part Number 550-142-902/1016