Function Parameter Index Reference
Static Configuration Parameters:
Table 5-55 ON/OFF Static Configuration Parameters
Parameter
Index
pv_hi
0
pv_lo
1
sp_hi_lim
6
sp_lo_lim
7
sp_rate_dn
9
sp_rate_up
10
devbar_hi
11
devbar_low
12
Output
13
Hysteresis
al_sp[4]
14-17
al_hyst
22
Fail Safe Out
23
86
Type
Description
REAL
pv High Range value –99999 to 99999 (default 100)
REAL
pv Low Range value –99999 to 99999 (default 0)
REAL
set point high limit, -99999 to 99999 (default 100)
REAL
set point low limit, -99999 to 99999 (default 0)
REAL
Set point low rate of change limit, 0 (off) to 99999 (eu/min)
REAL
Set point high rate of change limit, 0 (off) to 99999 (eu/min)
REAL
High scale value for deviation bar graph (0 to 99999) (default
100)
REAL
Low scale value for deviation bar graph [always = -devbar_hi]
REAL
Off – 0 to 10% of Input Span
REAL
alarm set points al1sp1, al1sp2, al2sp1, al2sp2, -99999 to 99999
(default 0)
REAL
alarm hysterysis 0 to 5 (%)
BOOL
Fail Safe Out = On/Off
RS232 Communications Reference Manual